NetSure™ 211 Series -48 VDC Battery Cabin
2.3 Mounting the Battery Cabinet The battery cabinet is designed to mount on a wall or a standard 19” or 23” wide relay rack.
The NetSureTM 211 Series -48 VDC battery cabinet can be mounted in a 23” relay rack or mounted to a wall. The battery cabinet contains one (1) 40 A battery disconnect circuit breaker and provides alarm leads attached to the common contacts of the breaker. Battery cabinets may be daisy chained as shown in Figure 7 to increase the reserve time.
THIS SYSTEM CONTAINS BATTERIES Although the DC voltage is not hazardously high, the battery can deliver large amounts of current. Exercise extreme caution not to inadvertently contact or have any tool inadvertently contact a battery terminal or exposed wire connected to a battery terminal.
However, a maximum system current of 30 amps should be maintained regardless of the number of interconnected cabinets. The battery cabinet is designed to hold the batteries listed in Table 1. Operating Ambient Temperature Range: -40 °C to +65 °C. Storage Ambient Temperature Range: -40 °C to +85 °C.
The battery cabinet is designed to hold the batteries listed in Table 1. Operating Ambient Temperature Range: -40 °C to +65 °C. Storage Ambient Temperature Range: -40 °C to +85 °C. Humidity: This unit is capable of operating in an ambient relative humidity range of 0% to 95%, non-condensing.